Insight

Can Quantitative Risk Assessment Improve Alternating Current Fault Mitigation Decisions?

Insight

Can Quantitative Risk Assessment Improve Alternating Current Fault Mitigation Decisions?

How Can Operators Make Better Integrity Decisions for Underground Gas Storage Wells?

Based on the technical paper “Using Quantitative Risk Assessment as an Alternative to Conventional AC Fault Mitigation”

When pipelines and high-voltage transmission lines share a right-of-way, operators must manage electrical hazards while ensuring mitigation resources are directed where they provide the greatest safety benefit.

Conventional AC fault screening methods identify locations where predicted touch voltages exceed defined limits. However, this does not necessarily mean that every location presents the same level of life-safety risk.

This raises an important question for operators:

Can alternating current fault mitigation decisions be based on quantified risk rather than applying the same response wherever a screening threshold is exceeded?

To answer that question, C-FER applied a quantitative risk assessment (QRA) framework to 39 farm tap units that had been identified for mitigation based on conventional screening. The results showed that most locations already met the defined risk criteria, while others could be addressed through targeted mitigation measures rather than a one-size-fits-all response.

Shared Corridors Create Different Alternating Current (AC)

The study evaluated 39 farm tap units located near high-voltage transmission infrastructure. All 39 sites had initially been identified for mitigation because predicted touch voltages exceeded conventional screening limits.

When the locations were assessed using a quantitative risk framework, the results were significantly different:

  • 31 sites already met the defined risk criteria under existing conditions.
  • Five sites could meet the criteria with properly maintained crushed rock.
  • Three sites required conventional copper grounding.

The recommended mitigations also maintained acceptable worker risk across the assessment area.

These findings demonstrate that locations with similar screening results may present very different levels of actual risk. By evaluating both the likelihood and consequence of a hazardous event, operators can better align mitigation measures with site-specific conditions.

Operator takeaway: Quantitative risk assessment can help distinguish between locations that require conventional mitigation, those where alternative controls may be sufficient, and those where existing risk is already acceptable.

Why Screening Alone Doesn’t Tell the Whole Story

Sharing a corridor can reduce the land required for infrastructure, but it also creates electrical interactions that must be understood and managed.

During a transmission-line fault caused by events such as lightning strikes, equipment failures, or conductor contact with the ground, electrical current can transfer to a nearby pipeline and energize aboveground facilities. If a person is touching the asset at that moment, they could become part of the path through which the current returns to ground, creating a potentially serious shock hazard.

Conventional screening methods are designed to identify where hazardous touch voltages could occur and remain an important first step in protecting workers and the public. However, they primarily indicate whether a voltage threshold is exceeded. They do not assess how likely a complete hazardous event is to occur.

For a fatal electrical shock to result, several conditions must happen at the same time:

  • A transmission-line fault must occur.
  • The fault must energize the pipeline facility.
  • A person must be present and touching the asset.
  • The resulting current must be sufficient to cause a severe injury or fatality.

Quantitative risk assessment evaluates the likelihood of those conditions occurring together. Rather than focusing only on voltage, it considers both probability and consequence to estimate individual risk and compare it against defined acceptance criteria.

Applying Risk-based Decision Making to AC Fault Hazards

The QRA framework adapted techniques commonly used in pipeline integrity management for threats such as corrosion, cracking, and mechanical damage.

The assessment considered:

  • Transmission-line fault frequencies.
  • The probability of human presence and contact.
  • Potential physiological consequences of electrical exposure.
  • The effectiveness of different mitigation options.

This approach allowed AC fault hazards to be evaluated using the same risk-based decision-making principles operators already use for other integrity threats.

A conservative risk target of 1 × 10⁻⁷ per year was used for the isolated AC fault threat. This represents 10% of the broadly acceptable individual risk threshold typically applied to the combined risks affecting people near a pipeline.

Public and Worker Risk Require Different Perspectives

Members of the public and pipeline workers may interact with the same facilities, but their exposure patterns differ significantly.

Public risk can generally be evaluated on a site-by-site basis because members of the public are unlikely to encounter multiple farm tap units. Worker exposure, however, may be cumulative because personnel often visit many sites as part of their normal duties.

For that reason, the project assessed public and worker risk separately. The results showed that mitigation measures sufficient to satisfy the public risk criteria also reduced worker risk below the defined target.

This distinction is important because it ensures mitigation decisions reflect how facilities are actually used and accessed in the field.

Where Crushed Rock Can Be An Effective Alternative

Copper grounding remains a well-established method of reducing AC fault hazards, but it can be extensive and costly.

The assessment found that crushed rock could provide sufficient risk reduction at five of the eight locations that initially exceeded the risk target. By increasing electrical resistance between a person and the ground, crushed rock can reduce the amount of current that passes through the body during a fault event.

However, its effectiveness depends on condition. Contamination, displacement, or degradation can reduce performance over time. Operators who take credit for crushed rock as a mitigation measure should support that decision with appropriate inspection and maintenance programs.

Where properly maintained, crushed rock may offer a practical alternative to more extensive grounding installations while still achieving acceptable risk levels.

Applying Risk-based Mitigation in Practice

The value of quantitative risk assessment extends beyond reducing unnecessary mitigation. It provides a stronger technical basis for prioritizing investments and demonstrating that mitigation decisions are proportionate to risk.

The approach can support:

  • Prioritization of AC fault mitigation projects.
  • Selection of site-specific mitigation measures.
  • Evaluation of public and worker exposure.
  • Capital planning for grounding installations.
  • Inspection and maintenance planning for crushed rock.
  • Documentation of the technical basis for mitigation decisions.

The quality of available data plays an important role in these assessments. Information such as fault frequencies, site conditions, worker activity records, and electrical system data can improve confidence in the results and reduce reliance on conservative assumptions.

Mitigation decisions should also be treated as iterative. Installing grounding at one location can alter electrical pathways and influence conditions elsewhere in the system. As a result, mitigation recommendations should be incorporated into updated AC interference analyses and reassessed to confirm that acceptable risk levels are maintained across the entire assessment area.

Better Risk Information Supports Better Pipeline Decisions

Conventional screening remains an essential tool for identifying potential AC fault concerns. Quantitative risk assessment adds another layer of insight by evaluating whether the conditions required for a serious consequence are likely to occur and whether proposed mitigations are proportionate to the risk.

For the locations evaluated, that additional information significantly changed the mitigation picture. Most sites initially identified for mitigation already met the defined risk criteria, while others could be addressed through targeted controls rather than extensive grounding installations.

For pipeline operators, the benefit is straightforward: maintain protection for workers and the public while directing mitigation investments to the locations where they will deliver the greatest risk reduction.

C-FER Supports Pipeline Operators Manage Integrity & Reliability

For decades, C-FER has helped industry understand and manage complex integrity and reliability challenges through our risk assessment expertise.  For underground gas storage assets, C-FER combines that expertise with our extensive well engineering experience to help operators:

  • Develop and enhance risk assessment frameworks
  • Evaluate well integrity risks and failure mechanisms
  • Support inspection, monitoring, and intervention planning
  • Support regulatory and stakeholder discussions with defensible technical analysis

As integrity management expectations continue to evolve, operators need tools that support consistent, transparent, and risk-informed decision-making. By combining historical data, engineering models, fault-tree analysis, and well-specific information, C-FER’s hybrid framework provides a practical path toward more quantitative risk assessment without requiring operators to abandon the knowledge and experience already embedded in their existing programs.

Contributor

Daniel Fujinaga, BSc
Engineering Manager, Integrity Management & Structures

Daniel Fujinaga the engineering manager for C-FER’s Integrity Management & Structures department. He holds a Bachelor of Science in Materials Engineering from the University of Alberta. Daniel’s expertise includes cathodic protection, materials engineering and data analysis.

Read more about Daniel.

Explore More